14.7  TROUBLESHOOTING WHEN INDOOR TIMER LAMP BLINKS 
14.7.1  MONOZONE / MULTIZONE INDOOR 
No 
Blinking of TIMER lamp 
Reason for indication 
Possible causes 
RAK  RAF 
RAI 
RAD 
 
  
When the indoor heat exchanger 
temperature is too low in the 
heating mode or it is too high in 
the cooling mode. 
Refrigerant cycle abnormal 
1)  Reversing valve defective 
2)  Heat exchanger thermistor 
disconnected (only in 
heating mode) 
The malfunction mode is 
displayed only after  the 
abnormal condition occurs 3
rd
 
time (read every 3 minutes 
•  Four-way valve faulty. 
*Note (for RAI & RAD) 
•  Disconnection in heat 
exchange thermistor 
(only during heating) 
★ 
★ 
★ 
★ 
 
 
When the outdoor unit is in 
forced operation or balancing 
operation after forced operation 
Outdoor unit forced operation. 
Electrical parts in the outdoor 
unit. 
★ 
★ 
★ 
★ 
 
When the interface signal from 
the outdoor unit is interrupted. 
Indoor/outdoor interface 
defective 
1)  Indoor interface circuit. 
2)  Outdoor interface circuit 
★ 
★ 
★ 
★ 
 
 
When the error mode is detected 
times within 30 minutes from 
outdoor unit electrical 
components. (However, when 
error is detected 8 times within 
two hours only for outdoor 
thermistor 
Outdoor electrical assembly 
defective 
Outdoor unit electrical 
components. (For details, 
operate again using remote 
controller and check from self-
diagnosis display of outdoor 
unit) 
★ 
★ 
★ 
★ 
 
All stop when the float switch 
has been activated 
Abnormal water level detection 
1)  Drain stopped up 
2)  Drain pump 
3)  Float switch 
 
 
★ 
★ 
 
 
When the knob of drain pump 
test switch at indoor P.W.B main 
slide to “test” position. 
Drain pump forced operation 
1)  Indoor PWB (Main) 
 
 
★ 
★ 
 
 
When room thermistor or heat 
exchanger thermistor is opened 
circuit or short circuit. 
Room thermistor or heat 
exchanger thermistor is faulty 
1)  Room thermistor 
2)  Heat exhanger thermistor 
★ 
★ 
★ 
★ 
10 
 
 
Overcurrent in indoor DC fan 
motor has been detected. 
Over-current detection at the DC 
fan motor 
1)  Indoor fan locked 
2)  Indoor fan  motor 
3)  Indoor control P.W.B. 
★ 
★ 
★ 
★ 
11 
 
 
When data read from IC401 or 
IC402 is incorrect. 
IC401 or IC402 data reading error  IC401 or IC402 abnormal 
★ 
★ 
★ 
★ 
*Note: Refer to Chapter 9 for error codes displayed on remote controllers. 
(
 Lights for 0.35 sec. at interval of 0.35 sec.) 
<Cautions> 
1)  If the interface circuit is faulty when power is supplied, the self diagnosis display will not be displayed 
2)  If the indoor unit does not operate at all, check if the connecting cable is connected to the outdoor unit. 
1 time 
2sec 
2sec 
2 times 
2sec 
3 times 
2sec 
4 times 
2sec 
6 times 
2sec 
7 times 
2sec 
9 times 
2sec  10 times 
2sec  13 times