Technical specification
63
I
ΔN × 1/2
I
ΔN × 1
I
ΔN × 2
I
ΔN × 5
RCD I
Δ
I
ΔN (mA) AC A B* AC A
B* AC A B
AC
A
B* AC
A
B*
10
5 3.5
5 10 20 20 20 40 40
50 100
100 9
9 9
30
15
10.5
15 30 42 60 60 84 120 150 212
300 9
9 9
100
50 35 50 100 141 200 200 282 400 500 707
1000 9
9 9
300
150
105 150 300 424 600 600 848 n.a. 1500 n.a.
n.a. 9
9 9
500
250 175 250 500 707 1000 1000 1410 n.a. 2500 n.a. n.a. 9
9 9
1000
500
350 500 1000
1410
n.a. 2000
n.a. n.a. n.a. n.a.
n.a. 9
9 n.a.
n.a......................................................not applicable
AC type..............................................sine wave test current
A type…… .........................................pulsed current
B type ................................................smooth DC current
9.3.2 Contact voltage RCD-Uc
AC type..............................................sine wave test current
A type…… .........................................pulsed current
B type ................................................smooth DC current
9.3.2 Contact voltage RCD-Uc
Measuring range according to EN61557 is 20.0 V
÷ 31.0V for limit contact voltage 25V
Measuring range according to EN61557 is 20.0 V
÷ 62.0V for limit contact voltage 50V
Measuring range (V)
Resolution (V)
Accuracy
0.0
÷ 19.9
0.1
(-0 % / +15 %) of reading ± 10 digits
20.0
÷ 99.9
(-0 % / +15 %) of reading
The accuracy is valid if mains voltage is stabile during the measurement and PE
terminal is free of interfering voltages.
Test current ...................................... max. 0.5
terminal is free of interfering voltages.
Test current ...................................... max. 0.5
×I
ΔN
Limit contact voltage ......................... 25 V, 50 V
Specified accuracy is valid for complete operating range.
9.3.3 Trip-out time
Specified accuracy is valid for complete operating range.
9.3.3 Trip-out time
Complete measurement range corresponds to EN 61557 requirements.
Maximum measuring times set according to selected reference for RCD testing.
Maximum measuring times set according to selected reference for RCD testing.
Measuring range (ms)
Resolution (ms)
Accuracy
0.0
÷ 40.0
0.1
±1 ms
0.0
÷ max. time *
0.1
±3 ms
* For max. time see normative references in
4.2.5 – this specification applies to max.
time >40 ms.
Test current ...................................... ½
Test current ...................................... ½
×I
ΔN
, I
ΔN
, 2
×I
ΔN
, 5
×I
ΔN
5
×I
ΔN
is not available for I
ΔN
=1000 mA (RCD type AC) or I
ΔN
≥ 300 mA (RCD types A,
B*).
2
2
×I
ΔN
is not available for I
ΔN
=1000 mA (RCD type A) or I
ΔN
≥ 300 mA (RCD type B*).
1
×I
ΔN
is not available for I
ΔN
=1000 mA (RCD type B)*.
Specified accuracy is valid for complete operating range.
9.3.4 Trip-out current
9.3.4 Trip-out current
Trip-out current
Complete measurement range corresponds to EN 61557 requirements.
Complete measurement range corresponds to EN 61557 requirements.
Measuring range I
Δ
Resolution
I
Δ
Accuracy
0.2
×I
ΔN
÷ 1.1×I
ΔN
(AC type)
0.05
×I
ΔN
±0.1×I
ΔN
0.2
×I
ΔN
÷ 1.5×I
ΔN
(A type, I
ΔN
≥30 mA)
0.05
×I
ΔN
±0.1×I
ΔN