TESTBOY TV 450 
Technical specification 
 
63 
 
I
ΔN × 1/2 
I
ΔN × 1 
I
ΔN × 2 
I
ΔN × 5 
RCD I
Δ 
I
ΔN (mA)  AC A  B*  AC  A 
B*  AC  A B 
AC 
B* AC 
B* 
10 
5 3.5 
5  10 20 20 20 40 40 
50 100 
100 9 
9 9
 
30 
15 
10.5 
15 30 42 60 60 84 120 150 212 
300 9 
9 9
 
100 
50 35  50  100 141 200 200 282 400 500 707 
1000 9 
9 9
 
300 
150 
105 150 300 424 600 600 848 n.a. 1500 n.a. 
n.a. 9 
9 9
 
500 
250 175  250  500  707  1000 1000 1410 n.a. 2500 n.a. n.a.  9 
9 9
 
1000 
500 
350 500 1000 
1410 
n.a. 2000 
n.a. n.a. n.a. n.a. 
n.a. 9 
9 n.a.
n.a......................................................not applicable 
AC type..............................................sine wave test current 
A type…… .........................................pulsed current 
B type ................................................smooth DC current 
 
9.3.2  Contact voltage RCD-Uc 
 
Measuring range according to EN61557 is 20.0 V 
÷ 31.0V for limit contact voltage 25V 
Measuring range according to EN61557 is 20.0 V 
÷ 62.0V for limit contact voltage 50V 
Measuring range (V) 
Resolution (V) 
Accuracy 
0.0 
÷ 19.9 
0.1 
(-0 % / +15 %) of reading ± 10 digits
 
20.0 
÷ 99.9 
 
(-0 % / +15 %) of reading 
The accuracy is valid if mains voltage is stabile during the measurement and PE 
terminal is free of interfering voltages. 
 
Test current ...................................... max. 0.5
×I
ΔN
 
Limit contact voltage ......................... 25 V, 50 V 
Specified accuracy is valid for complete operating range. 
 
9.3.3 Trip-out time 
 
Complete measurement range corresponds to EN 61557 requirements. 
Maximum measuring times set according to selected reference for RCD testing. 
Measuring range (ms) 
Resolution (ms) 
Accuracy 
0.0 
÷ 40.0 
0.1 
±1 ms 
0.0 
÷ max. time * 
0.1 
±3 ms 
* For max. time see normative references in 
4.2.5  – this specification applies to max. 
time >40 ms.  
 
Test current ...................................... ½
×I
ΔN
, I
ΔN
, 2
×I
ΔN
, 5
×I
ΔN 
5
×I
ΔN
 is not available for I
ΔN
=1000 mA (RCD type AC) or I
ΔN 
≥ 300 mA (RCD types A, 
B*). 
2
×I
ΔN
 is not available for I
ΔN
=1000 mA (RCD type A) or I
ΔN 
≥ 300 mA (RCD type B*). 
1
×I
ΔN
 is not available for I
ΔN
=1000 mA (RCD type B)*. 
Specified accuracy is valid for complete operating range. 
 
9.3.4 Trip-out current 
 
Trip-out current 
Complete measurement range corresponds to EN 61557 requirements. 
Measuring range I
Δ
 Resolution 
I
Δ
 
Accuracy 
0.2
×I
ΔN
 
÷ 1.1×I
ΔN
 (AC type) 
0.05
×I
ΔN
 
±0.1×I
ΔN
 
0.2
×I
ΔN
 
÷ 1.5×I
ΔN
 (A type, I
ΔN
 ≥30 mA) 
0.05
×I
ΔN
 
±0.1×I
ΔN