Phoenix Contact HART multiplexer MACX MCR-S-MUX 2865599 2865599 データシート

製品コード
2865599
ページ / 5
Nov 13, 2013    1 / 5
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in
the user's documentation. Our General Terms of Use for Downloads are valid
(http://download.phoenixcontact.com)
HART Multiplexer for online configuration and diagnostics of HART-compatible field devices, as well
as for continuous documentation of process variables and states with a PC or management system
for mounting on NS 35/7.5 or NS 32
 
Product Features
 Supports online configuration and diagnostics for the connected HART-compatible field devices
 Communication via software tool (e.g., HART OPC server) using RS-485 interface
 Up to 128 HART multiplexers on one PC interface
 32 HART channels per multiplexer
 Continuous documentation of process variables and states
 Electrical isolation between auxiliary voltage, RS-485 bus, and the HART channels
 HART field devices are accessed parallel to the transmission of the measurement signal without affecting measured value
processing
 HART field devices connected via universal HART connection boards; direct connection if processing non-Ex signals, with separate
Ex i signal isolator connected upstream if processing Ex signals
 Power supply via HART connection board
  
Key commercial data
package_quantity
1
GTIN
4046356153898
Technical data
Dimensions
Width
35.2 mm
Height
99 mm
Depth
114.5 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 60 °C
Ambient temperature (storage/transport)
-40 °C ... 80 °C
Max. permissible relative humidity (operation)
≤ 95 % (no condensation)
Field devices interface (HART)
Channels
16 or 32; adjustable using a switch
Connection method
Flat-ribbon cable, 14-pos. (inclusive)
Signal
HART FSK