Technical data
Field devices interface (HART)
HART specification
HART Field Communication Protocol Rev. 6.0 (downward
compatible up to Rev 4.0); FSK Physical Layer Specification (Rev.
8.1)
Data transmission display
Two yellow "Tx" and "Rx" "HART" LEDs
Display error
Red "ERR" LED (flashes in case of an error in the HART bus)
RS-485 interface
Connection method
D-SUB-9 female connector
Signal
RS-485
Data flow control/protocols
Compatible with OPC HART server, PDM, PRM, and FDT/DTM
Number of HART multiplexers per bus segment
Max 31
Address setting
0...127; using a rotary switch at the front
Data rate
9600 / 19200 / 38400 / 57600 [bps]; via rotary switch at the front
Transmission length
≤ 1200 m
Display
Two yellow "Tx" and "Rx" "RS-485" LEDs
General data
Supply voltage
24 V DC
Supply voltage range
18 V ... 31.2 V
Typical current consumption
55 mA
Nominal power consumption
1.35 W
Operating voltage display
Green "PWR" LED
Undervoltage monitoring
Yes (no faulty devices / output states)
Galvanic isolation of HART signal/RS-485
350 V AC
Galvanic isolation of HART signals between each other
100 V DC (Capacitive)
Galvanic isolation of HART signal/supply
350 V AC
Galvanic isolation of RS-485/supply
350 V AC
Error monitoring
Processor error: The "PWR" LED flashes; error in the HART
communication: the "ERR" LED flashes
Conformance
CE-compliant
classifications
eCl@ss
eCl@ss 4.0
27210107
eCl@ss 4.1
27210107
eCl@ss 5.0
27210107
eCl@ss 5.1
27210107
eCl@ss 6.0
27210107
eCl@ss 7.0
27210107
eCl@ss 8.0
27210107
ETIM
ETIM 2.0
EC000310