Secutech Radio modules ST002002 データシート

製品コード
ST002002
ページ / 40
Page 20
 
Security & Electronic Technologies GmbH
 
 
 
SECU-DATA 600M (NAMUR) 
 
Terminal  Signal, function 
1  Plus-pole of power supply (
+11 … +40 V), re-
verse polarity protection by two 2 diodes,  
igni
tion prevention level “ib“ 
2  Ground line of power supply (0 V) 
3   Positive pole for connection of the NAMUR-
probe. 
SECU-DATA 600M applies 8.2 V DC via  
1000 Ohms 
4   Negative pole for connection of the NAMUR 
probe 
5  Not connected 
6, 7, 8   Relay contacts, passive, for monitoring the sta-
tus of the RF-connection 
7 is the root, for active RF-connection terminals 
6-7 are interconnected, during RF-interruptions 
terminals 7-8 are interconnected. 
Rated switching capacity: 30 V / 500 mA 
 
SECU-DATA 500C / 1550C is used as the receiver, for the terminal connec-
tions see section SECU-DATA Relay on page 18 in this chapter. 
Functionality: 
The connected probe is tested for basic functionality: If the probe current is 
below 0.4 mA or higher than 6 mA, relay Re2 of the receiver SECU-DATA 
500C  is  activated  per  RF-connection,  the  contact  is  closed.  This  can  be 
used to issue an alarm message. The contact is connected to terminals 5, 6 
of the SECU-DATA 500C / 1500C. 
During  the  filling  process  the  contact  of  relay  Re1  SECU-DATA  500C  / 
1550C  is  also  closed  via  RF-signals  (probe  current  is  more  than  2  mA);  if 
the  tank  is  full  (filling  is  not  permissible,  probe  current  below  1  mA)  Re1 
opens. 