SECU-DATA 710M/710B (TRbF)
Terminal Signal, function
1 Plus-pole of power supply (+22
V … +40 V),
reverse polarity protection by two 2 diodes,
igni
igni
tion prevention level “ib“
2 Ground line of power supply (0 V)
3 Positive pole for connection of the barrier
SECU-DATA 710B for supplying the TRbF-
probe.
probe.
4 Negative pole for connection of the barrier
SECU-DATA 710B for supplying the TRbF-
probe.
probe.
5 Connection of the positive pole of the TRbF
probe
6 Connection of the negative pole of the TRbF
probe
7, 8 Relay contact, passive, for monitoring the status
of the RF-connection
For active RF-connection terminals 7-8 are in-
terconnected.
terconnected.
Rated switching capacity: 30 V / 500 mA
SECU-DATA 500C / 1500C is used as the receiver, for the connections see
section SECU-DATA Relay on page 18.
Important:
If the measurement data transmitter is installed in Ex-zone 1 the version
SECU-DATA 710M has to be used in combination with the barrier SECU-
DATA 125 (for supplying the SECU-DATA 710M) and the additional diode-
barrier SECU-DATA 710B (for supplying the TRbF-probe in Ex-zone 0) to
achieve the required ignition protection level.
See also the important application hint on page 19.