Secutech Radio modules ST002002 データシート

製品コード
ST002002
ページ / 40
Security & Electronic Technologies GmbH
 
Page 21 
 
 
 
SECU-DATA 710M/710B (TRbF) 
 
Terminal  Signal, function 
1  Plus-pole of power supply (+22 
V … +40 V), 
reverse polarity protection by two 2 diodes,  
igni
tion prevention level “ib“ 
2  Ground line of power supply (0 V) 
3   Positive pole for connection of the barrier 
SECU-DATA 710B for supplying the TRbF-
probe. 
4   Negative pole for connection of the barrier 
SECU-DATA 710B for supplying the TRbF-
probe. 
5  Connection of the positive pole of the TRbF 
probe 
6  Connection of the negative pole of the TRbF 
probe 
7, 8   Relay contact, passive, for monitoring the status 
of the RF-connection 
For active RF-connection terminals 7-8 are in-
terconnected. 
Rated switching capacity: 30 V / 500 mA 
 
SECU-DATA 500C / 1500C is used as the receiver, for the connections see 
section SECU-DATA Relay on page 18. 
 
Important: 
If  the  measurement  data  transmitter  is  installed  in  Ex-zone  1  the  version 
SECU-DATA  710M  has  to  be  used  in  combination  with  the  barrier  SECU-
DATA 125 (for supplying the SECU-DATA 710M) and the additional diode-
barrier  SECU-DATA  710B  (for  supplying  the  TRbF-probe  in  Ex-zone  0)  to 
achieve the required ignition protection level. 
See also the important application hint on page 19.