Novatek THREE-PHASE POWER LIMITER OM-310 OM-310 データシート

製品コード
OM-310
ページ / 28
- 21 - 
NOVATEK-ELECTRO
                                                                                                                                                       
ОМ-310
 
Fault code 2 
247 
 fault code  according to table 2.8 
 
value of parameter 2 
248 
 parameter value  according to table 2.8 
 
Fault time 2 
249 
two upper bytes 
 
250 
two lower bytes 
 
Fault code 3 
251 
 fault code  according to table 2.8 
 
value of parameter 3 
252 
 parameter value  according to table 2.8 
 
Fault time 3 
253 
two upper bytes 
 
 
254 
two lower bytes 
 
Fault code 4 
255 
 fault code  according to table 2.8 
 
value of parameter 4 
256 
 parameter value  according to table 2.8 
 
Fault time 4 
257 
two upper bytes 
 
258 
two lower bytes 
 
Fault code 5 
259 
 fault code  according to table 2.8 
 
value of parameter 5 
260 
 parameter value  according to table 2.8 
 
Fault time 5 
261 
two upper bytes 
 
262 
two lower bytes 
 
 
 
N o t e 1 - Fault time – is time period since the OM-310 power-on till the moment of the fault occurrence. Meas-
ured in minutes. 
N o t e 2 - 
Upon ОМ-310 delivery, or after factory settings reset (2.2.6), error code 40 and parameter value 
10000 are written in the log. 
 
2.4.4.7  Communication error handling 
When an error situation occurs at time of a frame receipt (parity error, frame error, chec
ksum error), the ОМ-310  
device does not return a response. 
When an error occurs in the format or in the value of the data transferred (unsupported function code, etc.),  
ОМ-310  receives the request frame and forms a response with the error indicator and code. A high-order function 
field bit inserted in the unit serves as error indicator. A separate field in the response is allocated for the error code. 
A response example is given in Fig. 2.5. Error codes are shown in Table 2.6. 
 
 
Figure 2.5 - Example of after-error response 
 
    Table 2.6  
 
ERROR 
CODE 
TITLE 
Description 
01h 
ILLEGAL FUNCTION 
Function code received cannot be processed by ОМ-310 
02h 
ILLEGAL DATA ADDRESS 
Data address in the query is not accessible by the given 
subordinate 
03h 
ILLEGAL DATA ADDRESS 
Value contained in the request data field is not a valid value 
for ОМ-310 
04h 
SLAVE DEVICE FAILURE 
While ОМ-310 attempted to perform the requested action, an 
unrecoverable error occurred 
05h 
ACKNOWLEDGE 
ОМ-310  accepted request and is processing it, but it re-
quires a long time.  Such response prevents master from 
timeout error generation. 
06h 
SLAVE DEVICE FAILURE 
ОМ-310 is busy with command processing. Master must re-
peat message later when the slave is free. 
07h 
NEGATIVE ACKNOWLEDGE 
ОМ-310 cannot perform the program function received in the 
request 
 
2.4.5  The load energize/de-energize remote control via RS-232/RS-485 interface. 
ОМ-310 operation in the remote control mode is defined by the  parameter. 
When 
=0, the load energize/de-energize remote control is prohibited.