Novatek THREE-PHASE POWER LIMITER OM-310 OM-310 データシート
製品コード
OM-310
- 21 -
NOVATEK-ELECTRO
ОМ-310
Fault code 2
247
fault code according to table 2.8
value of parameter 2
248
parameter value according to table 2.8
Fault time 2
249
two upper bytes
250
two lower bytes
Fault code 3
251
fault code according to table 2.8
value of parameter 3
252
parameter value according to table 2.8
Fault time 3
253
two upper bytes
254
two lower bytes
Fault code 4
255
fault code according to table 2.8
value of parameter 4
256
parameter value according to table 2.8
Fault time 4
257
two upper bytes
258
two lower bytes
Fault code 5
259
fault code according to table 2.8
value of parameter 5
260
parameter value according to table 2.8
Fault time 5
261
two upper bytes
262
two lower bytes
N o t e 1 - Fault time – is time period since the OM-310 power-on till the moment of the fault occurrence. Meas-
ured in minutes.
N o t e 2 -
Upon ОМ-310 delivery, or after factory settings reset (2.2.6), error code 40 and parameter value
10000 are written in the log.
2.4.4.7 Communication error handling
When an error situation occurs at time of a frame receipt (parity error, frame error, chec
When an error situation occurs at time of a frame receipt (parity error, frame error, chec
ksum error), the ОМ-310
device does not return a response.
When an error occurs in the format or in the value of the data transferred (unsupported function code, etc.),
ОМ-310 receives the request frame and forms a response with the error indicator and code. A high-order function
field bit inserted in the unit serves as error indicator. A separate field in the response is allocated for the error code.
A response example is given in Fig. 2.5. Error codes are shown in Table 2.6.
field bit inserted in the unit serves as error indicator. A separate field in the response is allocated for the error code.
A response example is given in Fig. 2.5. Error codes are shown in Table 2.6.
Figure 2.5 - Example of after-error response
Table 2.6
ERROR
CODE
CODE
TITLE
Description
01h
ILLEGAL FUNCTION
Function code received cannot be processed by ОМ-310
02h
ILLEGAL DATA ADDRESS
Data address in the query is not accessible by the given
subordinate
subordinate
03h
ILLEGAL DATA ADDRESS
Value contained in the request data field is not a valid value
for ОМ-310
04h
SLAVE DEVICE FAILURE
While ОМ-310 attempted to perform the requested action, an
unrecoverable error occurred
unrecoverable error occurred
05h
ACKNOWLEDGE
ОМ-310 accepted request and is processing it, but it re-
quires a long time. Such response prevents master from
timeout error generation.
quires a long time. Such response prevents master from
timeout error generation.
06h
SLAVE DEVICE FAILURE
ОМ-310 is busy with command processing. Master must re-
peat message later when the slave is free.
peat message later when the slave is free.
07h
NEGATIVE ACKNOWLEDGE
ОМ-310 cannot perform the program function received in the
request
request
2.4.5 The load energize/de-energize remote control via RS-232/RS-485 interface.
ОМ-310 operation in the remote control mode is defined by the parameter.
When
ОМ-310 operation in the remote control mode is defined by the parameter.
When
=0, the load energize/de-energize remote control is prohibited.