Novatek THREE-PHASE POWER LIMITER OM-310 OM-310 データシート

製品コード
OM-310
ページ / 28
- 23 - 
NOVATEK-ELECTRO
                                                                                                                                                       
ОМ-310
 
Table 2.8  -  Fault codes 
                                                                                                     
Fault description 
Fault mne-
monic 
Parameter value 
Parameter 
value reg-
ister ad-
dress 
Fault 
code 
 
Register 
address 
bit 
№ 
de-energizing based on main 
threshold crossing 

Main threshold value 
in 100* W 
300 
241:0 
additional threshold crossing  

additional threshold 
value in 100* W 
301 
241:1 
maximum phase current fault 

maximum phase cur-
rent 
302 
241:2 
against line-to-earth fault 
(based on zero sequence 
current) 

zero sequence current 
303 
241:3 
currents present when load 
relay is de-energized (contac-
tor fault)  

current  
304 
241:4 
phase sequence order fault 

 
 
241:5 
minimum line voltage fault 


voltage 
306 
241:6 
maximum line voltage fault 


voltage 
307 
241:7 
phase imbalance fault 

 
imbalance  
308 
241:8 
 remote control channel fault 

 
 
241:9 
emergency load de-energize, 
automatic restart not possible 

 
 
10 
241:10 
emergency de-energize of load 
, automatic restart possible by 
simultaneous pressing buttons 
UP and DOWN 

 
 
11 
241:11 
Emergency load de-energizing 
by the remote breaker 

 
 
12 
241:12 
 
The SETUP LED will start to flicker, and the 
ОМ-310  indicator panels will display line 1 from Table 2.9. Log 
scrolling performed by pressing UP and DOWN buttons. 
To exit log view mode press RECORD/RESET/SELECT button, or the log will close automatically after 30 sec 
since last button was pressed. 
Fault information is displayed on 
ОМ-310  device indicators as shown below in  table 2.9. 
 
Table 2.9 
 
Mnemonic indicator output 
Value indicator output 
” 
number of log record (1- latest record) 
XXX – fault mnemonic according 
to table 2.8 
YYY - parameter value  according to table 2.8 
(if parameter value is negative, “----“ is displayed) 
XXX  - hours since fault 
YY  - number of minutes since fault occurrence 
 
2.4.9 Load start/cutoff control with use of OM-310 front panel 
Depending on the 
  parameter value, the 
ОМ-310 load relay can be controlled by pressing buttons UP and 
DOWN simultaneously (unless 
ОМ-310 is in keypad lock-up mode): 
=0 – no response; 
=1 (load energizing permitted) – load relay will close, if AR time has not expired; 
 
=2 ( emergency load de-energize) –load relay will open and produce “” fault code.  Load restart is possi-
ble after disconnecting and re-connecting power to OM-310; 
=3 (load energizing and de-energizing permitted) – load relay will open and produce “” fault code. To 
close, press UP and DOWN buttons again. 
 
N o t e -When parameters “=0”  (after power-on, load is energized manually via 
ОМ-310 control panel) 
and “
=0” (load energizing manual control forbidden) are selected, the load relay will not close.