Sample applications 
 
4.3 Heating control 
LOGO!Soft Comfort Online Help 
Operating Instructions, 06/2014 
185
 
LOGO!Soft Comfort Solution 
 
 
A PT100 sensor is connected to AI1 which measures the flow temperature. 
 
The parameters for the analog amplifier are as follows: 
• 
Sensor: PT100 
• 
The PT100 sensors stipulate the measuring range and parameters. 
• 
Unit: Celsius 
• 
Resolution: x 1 
The amplifier causes the actual temperature that the sensor has measured to be issued as the 
output. 
 
A PT100 sensor is connected to AI2 which measures the outdoor temperature. 
 
The parameters for the analog amplifier are as follows: 
• 
Sensor: PT100 
• 
The PT100 sensors stipulate the measuring range and parameters. 
• 
Unit: Celsius 
• 
Resolution: x 1 
The amplifier causes the actual temperature that the sensor has measured to be issued as the 
output. 
 
The parameters for the analog amplifier are as follows: 
• 
Sensor: No sensor 
• 
Gain: -1 (changes the sign of the value of the analog amplifier output from B001) 
• 
Offset: 50 
The parameters of the amplifier at B004 cause the difference of the compared temperatures of 
the comparator at B005 to be 0 if the sum of both temperatures is 50.