5.3 Special functions 
 
LOGO!Soft Comfort Online Help 
236
 
Operating Instructions, 06/2014 
 
 
0BA2, 0BA3: 
Only the T
L
 and T parameters exist. 
The output is reset when T has expired. 
T
L
 determines the period during which the input must be set in order to enable 
the permanent light function. 
Input R is not available to the user. 
 
 
 
Description of the function 
Output Q is set to 1 with a 0 to 1 signal transition at Trg. 
If output Q = 0, and input Trg is set hi for at least the duration of T
L
, the permanent lighting 
function is enabled and output Q is set accordingly. 
The off-delay time T is triggered when the status at input Trg changes to 0 before the time T
L
 
has expired. 
Output Q is reset when the Ta = T.  
You can output an off-warning signal prior to the expiration of the off-delay time (T - T
!
) that 
resets Q for the duration of the off prewarning time T
!L
. A subsequent signal at input Trg 
always resets T and output Q. 
Caution 
The time base for T, T
!
 and T
!L
 must be identical. 
5.3.1.12 
Weekly timer 
 
Caution 
Your LOGO! must be equipped with an internal real-time clock if you are going to use this 
SFB.