Reference material 
 
5.3 Special functions 
 
LOGO!Soft Comfort Online Help 
234
 
Operating Instructions, 06/2014 
Description of the function 
Output Q is set to 1 with a 0 to 1 signal transition at input Trg. The 1 to 0 transition at input 
Trg triggers the current time and output Q remains set. 
Output Q is reset to 0 when Ta reaches the time T. Before the off delay time (T - T
!
) has 
expired, you can output a prewarning that resets Q for the duration of the off prewarning time 
T
!L
Ta is retriggered (optional) at the next high/low transition at input Trg and if Ta is expiring. 
Scan cycle time 
For information on how to determine the scan cycle time of a LOGO!, refer to the appendix of 
the 
LOGO! Manual
5.3.1.11 
Multiple function switch 
 
Short description 
Switch with two different functions:  
●  Pulse switch with off delay 
●  Switch (continuous light) 
 
Connection 
Description 
Input Trg 
A signal at input Trg (Trigger) sets output Q (permanent light) or resets Q with an 
off-delay. When active, output Q can be reset with a signal at input Trg. 
Input R 
A signal at input R resets the current time Ta and resets the output. 
Parameter 
T : determines the off-delay time. The output is reset (1 to 0 transition) when the 
time T expires. 
T
L
 : determines the period during which the input must be set in order to enable 
the permanent light function. 
T
!
 : determines the on delay for the prewarning time. 
T
!L
 : determines the length of the prewarning time period. 
Retentivity on = the status is retentive in memory. 
Output Q 
Output Q is set with a signal at input Trg, and it is reset again after a configured 
time has expired and depending on the pulse width at input Trg, or it is reset with 
another signal at input Trg.