Stopwatch (0BA7 and 0BA8 only) 
 
Short description 
The stopwatch records the time elapsed since it was enabled.  
 
Connection 
Description 
Input En 
En (Enable) is the monitoring input. LOGO! sets the current elapsed time to 0 and 
begins counting elapsed time when En transitions from 0 to 1. When En transitions 
from 1 to 0, the elapsed time is frozen. 
Input Lap 
A positive edge (0 to 1 transition) at input Lap pauses the stopwatch, and sets 
output to lap time. A negative edge (1 to 0 transition) at input Lap resumes the 
stopwatch, and set the output to current elapsed time. 
Input R 
A signal at input R (Reset) clears the current elapsed time and lap time.  
Parameter 
Time base for elapsed time, which you can set to hours, minutes, seconds, or 
1/100ths of seconds. 
Output AQ 
The output AQ outputs value of the current elapsed time when it is a negative edge 
(1 to 0 transition) at the input Lap, and outputs value of the Lap time when it is a 
positive edge (0 to 1 transition) at the input Lap. 
A positive edge (0 to 1 transition) resets the value at output AQ to 0.  
Parameters Time base 
You can configure the time base for the analog output: 
 
The time base for the elapsed time can be in hours, minutes, seconds, or 1/100ths of 
seconds (units of 10 milliseconds). The smallest time base, and therefore the resolution, is 
10 milliseconds, or 1/100ths of seconds.