5.3 Special functions 
 
LOGO!Soft Comfort Online Help 
246
 
Operating Instructions, 06/2014 
Timing diagram 
 
Description of the function 
When En = 1, the current time increases. 
When En = 0, the current time counting pauses. 
When En = 1 and Lap = 0, the output AQ outputs the value of the current elapsed time. 
When En = 1 and Lap = 1, the current time continue increasing, but the output AQ outputs 
the value of the Lap time. 
When En = 0 and Lap =1, the output AQ outputs the value of the Lap time. 
When En = 0 and Lap = 0, the output AQ outputs the value of the latest current time. 
When R = 1, both the current time and the Lap time are reset. 
Special functions (Page 212)