5.3 Special functions 
LOGO!Soft Comfort Online Help 
Operating Instructions, 06/2014 
253
 
If the Retentivity option is not available, then delete the block and insert a new special 
function hours counter at the same position. 
 
 
0BA0-0BA5: 
The maintenance interval (MI) and the start time for the operating time (OT) 
were in units of hours. These values could not be provided by another function 
prior to the 0BA6 device series. 
Value reset 
If you download a circuit program that contains an hours counter function from LOGO!Soft 
Comfort to a LOGO! 0BA7 or LOGO! 0BA8 Base Module, LOGO!Soft Comfort prompts you 
whether to continue or not. If you continue with the download, the hours counter value is 
reset. 
 
 
 
 
Note 
If you copy a circuit program that contains an hours counter function from an SD card to a 
LOGO! Base Module, the hours counter value is reset with no notification. 
 
5.3.2.3 
Threshold trigger 
 
Short description 
The output is switched on and off depending on two configurable frequencies.  
 
Connection 
Description 
Input Fre 
The function counts 0 to 1 transitions at input Fre. Transitions from 1 to 0 are not 
counted. 
• 
Use the inputs I3, I4, I5, and I6 for high-frequency counts (LOGO! 
12/24RC/RCo, LOGO! 12/24RCE, LOGO! 24/24o and LOGO! 24C/24Co): 
max 5kHz, if the fast input is directly connected to the threshold trigger 
function block 
• 
Use any other input or circuit element for low frequencies (typical 4 Hz).