Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 データシート

製品コード
6ED1057-3BA00-0AA8
ページ / 378
 
Reference material 
 
5.3 Special functions 
LOGO!Soft Comfort Online Help 
Operating Instructions, 06/2014 
255
 
Timing diagram 
 
Description of the function 
The trigger measures the signals at input Fre. The pulses are captured during a configurable 
period G_T.  
Q is set or reset according to the set thresholds. See the following calculation rule. 
Calculation rule 
●  If the threshold (On) ≥ threshold (Off), then: 
Q = 1, if fa > On 
Q = 0, if fa ≤ Off. 
●  If the threshold (On) < threshold (Off), then Q = 1, if 
On ≤ fa < Off. 
5.3.3 
Analog 
5.3.3.1 
Analog threshold trigger 
 
Short description 
The output is set or reset depending on two configurable thresholds (hysteresis).  
 
Connetion 
Description 
Input Ax 
Input Ax is one of the following analog signals: 
• 
AI1 to AI8 
(
*
)
 
• 
AM1 to AM6 (if 0BA6), AM1 to AM16 (if 0BA7), or AM1 to AM64 (if 0BA8) 
• 
NAI1 to NAI32 (if 0BA7 or 0BA8) 
• 
AQ1 and AQ2 (if 0BA7), or AQ1 to AQ8 (if 0BA8) 
• 
NAQ1 to NAQ16 (if 0BA7 or 0BA8) 
• 
The block number of a function with analog output