Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 データシート

製品コード
6ED1057-3BA00-0AA8
ページ / 378
Reference material 
 
5.3 Special functions 
 
LOGO!Soft Comfort Online Help 
258
 
Operating Instructions, 06/2014 
 
 
0BA2, 0BA3: 
The function is as follows: 
The offset parameter is added to the read analog value. The sum is multiplied by 
the value of the gain parameter. 
Value = (AI+offset)*gain 
Output Q is set to 1 if the calculated value exceeds the on threshold (TH high). 
Q is reset to 0 when the value reaches or drops below the off threshold (TH low). 
Calculation rule 
●  If threshold (On) ≥ threshold (Off), then: 
Q = 1, if the actual value Ax > On 
Q = 0, if the actual value Ax ≤ Off. 
●  If threshold (On) < threshold (Off), then Q = 1, if 
On ≤ the actual value Ax < Off.