Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 数据表
产品代码
6ED1057-3BA00-0AA8
Reference material
5.3 Special functions
LOGO!Soft Comfort Online Help
258
Operating Instructions, 06/2014
0BA2, 0BA3:
The function is as follows:
The offset parameter is added to the read analog value. The sum is multiplied by
the value of the gain parameter.
Value = (AI+offset)*gain
Output Q is set to 1 if the calculated value exceeds the on threshold (TH high).
Q is reset to 0 when the value reaches or drops below the off threshold (TH low).
Calculation rule
● If threshold (On) ≥ threshold (Off), then:
Q = 1, if the actual value Ax > On
Q = 0, if the actual value Ax ≤ Off.
● If threshold (On) < threshold (Off), then Q = 1, if
On ≤ the actual value Ax < Off.