Reference material 
 
5.3 Special functions 
 
LOGO!Soft Comfort Online Help 
264
 
Operating Instructions, 06/2014 
Timing diagram 
 
Description of the function 
The function reads the value of the signal at the analog input Ax.  
This value is multiplied by the value of parameter A (gain). Parameter B (offset) is added to 
the product, hence 
(Ax * gain) + offset = Actual value Ax.  
(Ay * gain) + offset = Actual value Ay. 
Output Q is set or reset depending on the difference of the actual values Ax – Ay and the set 
thresholds. See the following calculation rule. 
Calculation rule 
●  If threshold On ≥ threshold Off, then: 
Q = 1, if (actual value Ax - actual value Ay) > On 
Q = 0, if (actual value Ax - actual value Ay) ≤ Off. 
●  If threshold On < threshold Off, then Q = 1, then: 
On ≤ (actual value Ax - actual value Ay) < Off. 
 
 
0BA2, 0BA3: 
The following functions/calculation rules apply: 
The function adds the relevant specified offset to the analog values Ax and Ay. 
The sum is multiplied with the value of the gain parameter. The difference is 
formed from both calculated values. 
Output Q is set if this difference between these values exceeds the threshold 
you have configured under delta. 
Calculation rule: 
Q = 1, if: 
((Ax + offset) * gain) - ((Ay + offset)*gain) > threshold delta 
Q is reset to 0 when the threshold reaches or drops below delta.