5.3 Special functions 
LOGO!Soft Comfort Online Help 
Operating Instructions, 06/2014 
265
 
Reducing the input sensitivity of the analog comparator 
You can delay the output of the analog comparator selectively by means of the "on delay" 
and "off delay" SFBs. By doing so, you determine that output Q is only set if the input trigger 
length Trg (= output of the analog comparator) exceeds the defined on delay time. 
This way you can set a virtual hysteresis, which renders the input less sensitive to short 
changes. 
Particular characteristics to be noted when configuring 
For help on analog block parameters, refer to the Analog value processing (Page 286) 
5.3.3.4 
Analog watchdog 
 
Short description 
This special function saves the process variable of an analog input to memory, and sets the 
output when the output variable exceeds or drops below this stored value plus a configurable 
offset.  
 
Connection 
Description 
Input En 
A positive edge (0 to 1 transition) at input En saves the analog value at input Ax 
("Aen") to memory and starts monitoring of the analog range Aen +- Delta. 
Input Ax 
Input Ax is one of the following analog signals: 
• 
AI1 to AI8 
(
*
)
 
• 
AM1 to AM6 (if 0BA6), AM1 to AM16 (if 0BA7), or AM1 to AM64 (if 0BA8) 
• 
NAI1 to NAI32 (if 0BA7 or 0BA8) 
• 
AQ1 and AQ2 (if 0BA7), or AQ1 to AQ8 (if 0BA8) 
• 
NAQ1 to NAQ16 (if 0BA7 or 0BA8) 
• 
The block number of a function with analog output 
Parameter 
Gain 
Range of values: -10.00 to 10.00 
Offset 
Range of values: -10000 to 10000 
Threshold 1: Difference value above Aen: on/off threshold 
Range of values: 0 to 20000 
Threshold 2: Difference value below Aen: on/off threshold 
Range of values: 0 to 20000 
p: Number of decimals 
Possible settings: 0, 1, 2, 3 
Retentivity on = the status is retentive in memory.