Particular characteristics to be noted when configuring 
For help on analog block parameters, refer to the Analog value processing (Page 286) 
section. 
Analog output 
If you connect this special function to a real analog output, then note that the analog output 
can only process values from 0 to 1000. To do this, connect an additional amplifier between 
the analog output of the special function and the real analog output. With this amplifier you 
standardize the output range of the special function to a value range of 0 to 1000. 
Example: additional amplifier behind an analog multiplexer. 
 
5.3.3.6 
Analog multiplexer 
 
Short description 
When enabled, the analog multiplexer SFB displays one of four pre-defined analog values, 
depending on input conditions.  
 
Connection 
Description 
Input En 
1 on input En (Enable) switches, dependent on S1 and S2, a parameterized 
analog value to the output AQ. 
0 on input EN switches 0 to the output AQ. 
Inputs S1 
and S2 
S1 and S2 (selectors) for selecting the analog value to be issued. 
S1 = 0 and S2 = 0: The value V1 is issued 
S1 = 0 and S2 = 1: The value V2 is issued 
S1 = 1 and S2 = 0: The value V3 is issued 
S1 = 1 and S2 = 1: The value V4 is issued 
Parameter 
V1 to V4: Analog values (Value) that will be issued. 
Value range: -32768 to +32767 
p: Number of decimal places 
Possible settings: 0, 1, 2, 3 
Output AQ 
Analog output 
Value range for AQ: -32768 to +32767