5.3 Special functions 
 
LOGO!Soft Comfort Online Help 
288
 
Operating Instructions, 06/2014 
Gain 
The standardized value is multiplied with a parameter. Using this parameter you can boost 
the electric quantity; hence, this parameter is called the "gain". 
Zero point offset 
You can add or subtract a parameter to or from the boosted standardized value. 
Using this parameter you can move the zero point of the electric quantity; hence, this 
parameter is called the "zero point offset". 
Gain and offset 
The analog value is therefore calculated as follows: 
Analog value = (standardized value x gain) + offset 
The following diagram illustrates this formula and the significance of gain and offset: 
 
The straight line in the graphic describes which standardized value is being converted into 
which analog value. Gain corresponds to the slope of the straight line and offset to the 
movement of the zero point of the straight line on the y-axis. 
Analog output 
If you connect a special function (that has an analog output) to a real analog output, then 
note that the analog output can only process values from 0 to 1000. 
Possible settings with LOGO!Soft Comfort (Page 289)  
Possible settings with LOGO! (Page 290)  
Example: Heating Control (Page 291)