5.3 Special functions 
LOGO!Soft Comfort Online Help 
Operating Instructions, 06/2014 
289
 
5.3.4.2 
Possible settings with LOGO!Soft Comfort 
Sensor 
Set your sensor type. (0 V to 10 V; 0 mA to 20 mA; 4 mA to 20 mA; PT100/PT1000; no 
sensor)  
With sensor type 4 mA to 20 mA the value range for the standardized value is 200 and 1000. 
Measurement range 
Stipulate the measurement range. The measurement range is the value range shown for the 
analog value. 
 
LOGO!Soft Comfort then automatically calculates the gain and offset from this. 
Gain and offset 
If you want to set the gain, you can enter values between -10.00 and 10.00. The value 0 
makes no sense, as, irrespective of the applied analog value, you will always obtain the 
value 0 as a result. 
If you wish to set the offset, enter values between -10000 and 10000. 
Rounding error 
LOGO!Soft Comfort calculates the gain and zero point offset with utmost precision, while 
LOGO! calculates internally using whole numerical values; therefore, not all parameter 
combinations are possible on LOGO!. In this case, prior to transferring to LOGO!, LOGO!Soft 
Comfort detects a rounding error and proposes a possible replacement value range.