PI controller
Short description
A PI controller is a proportional-action and integral-action controller. You can use both
proportional action and integral action individually or combined.
Connection
Description
Input A/M
Set the mode of the controller:
1: automatic mode
0: manual mode
Input R
Use the input R to reset the output AQ. As long as this input is set, the input A/M
is disabled. The output AQ is set to 0.
Input PV
Analog value: process value, influences the output
Parameter
Sensor: Type of sensor being used
Min.: Minimum value for PV
Min.: Minimum value for PV
Value range: -10,000 to +20,000
Max.: Maximum value for PV
Max.: Maximum value for PV
Value range: -10,000 to +20,000
Gain
Gain
Value range: -10.00 to +10.00
Offset
Offset
Value range: -10,000 to +10,000
SP: Set-value assignment
SP: Set-value assignment
Value range: -10,000 to +20,000
Mq: Value from AQ with manual mode.
Mq: Value from AQ with manual mode.
Value range: 0 to 1,000
Parameter sets: application-related presets for KC, TI and Dir (see below)
KC: Gain
Parameter sets: application-related presets for KC, TI and Dir (see below)
KC: Gain
Value range: 00.00 to 99.99
TI: Integral time
TI: Integral time
Value range 00:01 min to 99:59 min
Dir: Action direction of the controller
Dir: Action direction of the controller
Possible settings: + or -
p: Number of decimal places
p: Number of decimal places
Possible settings: 0, 1, 2, 3
Output AQ
Analog output (manipulated variable)
Value range for AQ: 0 to 1,000