5.3.5.5 
Analog ramp 
 
Short Description 
The Analog Ramp instruction allows the output to be changed from the current level to the 
selected level at a specified rate.  
 
Connection 
Description 
Input En 
A change in the status from 0 to 1 at input En (Enable) applies the start/stop 
level (Offset "B" + StSp) to the output for 100 ms and starts the ramp operation 
to the selected level. 
A change in the status from 1 to 0 immediately sets the current level to Offset 
"B", which makes output AQ equal to 0. 
Input Sel 
SeI = 0: The step 1 (level 1) is selected. 
SeI = 1: The step 2 (level 2) is selected. 
A change in status of Sel causes the current level to start changing to the 
selected level at the specified rate. 
Input St 
A change in the status from 0 to 1 at input St (Decelerated Stop) causes the 
current level to decrease at a constant rate until the start/stop level (Offset "B" + 
StSp) is reached. The start/stop level is maintained for 100 ms and then the 
current level is set to Offset "B", which makes output AQ equal to 0. 
Parameter 
L1 and L2: Levels to be reached; value range for each level: -10000 to 20000 
MaxL: Maximum value that must not be exceeded. 
Value range: -10000 to 20000 
StSp: Start/Stop offset: value that is added to Offset "B" to create the start/stop 
level. If the Start/Stop offset is 0, then the start/stop level is Offset "B"). 
Value range: 0 to 20000 
Rate: Speed with which level 1, level 2 or offset is reached. Steps/seconds are 
issued. 
Value range: 1 to 10000 
Gain 
Value range: 0 to 10.00 
Offset 
Value range: -10000 to 10000 
p: Number of decimal places 
Possible settings: 0, 1, 2, 3 
Output AQ 
The output AQ is scaled using the formula: 
(Current Level - Offset "B") / Gain "A" 
Note: when AQ is displayed in parameter mode or message mode, it is displayed 
as an unscaled value (engineering units: current level). 
Value range for AQ: 0 to 32767