LOGO! functions 
 
4.4 Special functions list - SF 
 
LOGO! 
140
 
Manual, 06/2014, A5E33039675 
4.4.2 
Off-delay 
Short description 
When an on-delay (Page 136) is set, the output is reset when the configured time has 
expired.  
 
Symbol in LOGO! 
Wiring 
Description 
 
Input Trg 
The off-delay timer starts with a negative edge (1 to 0 
transition) at input Trg (Trigger) 
Input R 
A signal at input R resets the on-delay time and the 
output. 
Parameter 
The output switches off (transitions from1 to 0) when 
the delay time T expires. 
Retentivity:  
/ = No retentivity 
R = The status is retentive. 
Output Q 
A signal at input Trg sets Q. Q holds this state until T 
expires. 
Parameter T 
Note the parameter T defaults specified in topic Time response (Page 128). 
The actual value of another already-configured functions can provide the time for parameter 
T. You can use the actual value of the following functions:  
●  Analog comparator (Page 188) (actual value Ax - Ay) 
●  Analog threshold trigger (Page 183) (actual value Ax) 
●  Analog amplifier (Page 195) (actual value Ax) 
●  Analog multiplexer (Page 213) (actual value AQ) 
●  Analog ramp (Page 216) (actual value AQ) 
●  Mathematic instruction (Page 227) (actual value AQ) 
●  PI controller (Page 220) (actual value AQ) 
●  Up/down counter (Page 173) (actual value Cnt) 
●  Analog filter (Page 232) (actual value AQ) 
●  Average value (Page 237) (actual value AQ) 
●  Max/Min (Page 234) (actual value AQ) 
●  On-delay (Page 136) (current time Ta) 
●  Off-delay (current time Ta) 
●  On-/off-delay (Page 142) (current time Ta) 
●  Retentive on-delay (Page 144) (current time Ta) 
●  Wiping relay (pulse output) (Page 146) (current time Ta)