LOGO! functions 
 
4.4 Special functions list - SF 
 
LOGO! 
142
 
Manual, 06/2014, A5E33039675 
4.4.3 
On-/off-delay 
Short description 
The on-/off-delay function sets the output after the set on-delay time has expired, and resets 
it upon expiration of the off-delay time.  
 
Symbol in LOGO! 
Wiring 
Description 
 
Input Trg 
A positive edge (0 to 1 transition) at input Trg 
(Trigger) triggers the on-delay time T
H
A negative edge (1 to 0 transition) at input Trg 
(Trigger) triggers the off-delay time T
L
Parameter 
T
H
 is the time after which the output is set hi (output 
signal transition 0 to 1). 
T
L
 is the time after which the output is reset ( output 
signal transition 1 to 0). 
Retentivity:  
/ = No retentivity 
R = The status is retentive. 
Output Q 
LOGO! sets Q when the configured time T
H
 expires 
and Trg is still set. LOGO! resets Q when T
L
 expires, 
if the trigger Trg has not been set. 
Parameters T
H
 and T
L
 
Note the preset values for the parameters T
H
 and T
L
 in topic Time response (Page 128). 
The actual value of another, already-configured function can provide the on-delay and off-
delay times for parameters T
H
 and T
. You can use the actual values of the following 
functions:  
●  Analog comparator (Page 188)(actual value Ax - Ay) 
●  Analog threshold trigger (Page 183)(actual value Ax) 
●  Analog amplifier (Page 195)(actual value Ax) 
●  Analog multiplexer (Page 213)(actual value AQ) 
●  Analog ramp (Page 216)(actual value AQ) 
●  Mathematic instruction (Page 227) (actual value AQ) 
●  PI controller (Page 220)(actual value AQ) 
●  Up/down counter (Page 173)(actual value Cnt) 
●  Analog filter (Page 232) (actual value AQ) 
●  Average value (Page 237) (actual value AQ) 
●  Max/Min (Page 234) (actual value AQ) 
●  On-delay (Page 136)(current time Ta) 
●  Off-delay (Page 140)(current time Ta)