LOGO! functions 
 
4.4 Special functions list - SF 
LOGO! 
Manual, 06/2014, A5E33039675 
143
 
●  On-/off-delay (current time Ta) 
●  Retentive on-delay (Page 144)(current time Ta) 
●  Wiping relay (pulse output) (Page 146)(current time Ta) 
●  Edge-triggered wiping relay (Page 148)(current time Ta) 
●  Asynchronous pulse generator (Page 150)(current time Ta) 
●  Stairway lighting switch (Page 154)(current time Ta) 
●  Multiple function switch (Page 156)(current time Ta) 
●  Stopwatch (Page 171)(actual value AQ) 
●  Threshold trigger (Page 180) (actual value Fre) 
Select the required function by the block number. The timebase is configurable. For 
information on valid timebase ranges and parameter preset, refer to Section "On-delay 
(Page 136)". 
Timing diagram 
 
Functional description 
The time T
H
 is triggered with a 0 to 1 transition at input Trg. 
If the status at input Trg is 1 at least for the duration of the time T
H
, LOGO! sets the output to 
1 on expiration of the time T
H
 (the output follows the input with on-delay). 
LOGO! resets the time when LOGO! resets the signal at input Trg to 0 before the time T
H
 
expires. 
A 1 to 0 transition at input Trg triggers the time T
L
If the status at input Trg is 0 at least for the duration of the signal T
L
, LOGO! sets the output 
to 0 on expiration of the time T
L
 (the output follows the input with off-delay). 
LOGO! resets the time when the signal at input Trg changes to 1 again before the time T
L
 
expires. 
If the block is retentive, LOGO! resets output Q and the expired time to the values before a 
power failure; if the block is not retentive, LOGO! resets output Q and the expired time to 
defaults after a power failure.