4.4 Special functions list - SF 
 
LOGO! 
152
 
Manual, 06/2014, A5E33039675 
4.4.8 
Random generator 
Short description 
The random generator function sets an output randomly within a configured time.  
 
Symbol in LOGO! 
Wiring 
Description 
 
Input En 
A positive edge ( 0 to 1 transition) at input En 
(Enable) triggers the on-delay time of the random 
generator. 
A negative edge ( 1 to 0 transition) at input En 
(Enable) triggers the off-delay time of the random 
generator. 
Parameter 
LOGO! sets the on-delay at random to a value 
between 0 s and T
H
The off-delay is set at random to a value between 0 s 
and T
L
Output Q 
LOGO! sets output Q when the on-delay expires and 
if En is still set. LOGO! resets Q when the off-delay 
expires, provided LOGO! has not set En again 
meanwhile. 
Parameter T
H
 and T
L
 
Note the defaults of the T
H
 and T
L
 parameters listed in topic Time response (Page 128). 
The actual value of another already-programmed function can provide the on-delay time TH 
and the off-delay time TL. You can use the actual values of the following functions:  
●  Analog comparator (Page 188) (actual value Ax – Ay) 
●  Analog threshold trigger  (Page 183) (actual value Ax) 
●  Analog amplifier (Page 195) (actual value Ax) 
●  Analog multiplexer (Page 213) (actual value AQ) 
●  Analog ramp (Page 216) (actual value AQ) 
●  Mathematic instruction (Page 227) (actual value AQ) 
●  PI controller (Page 220) (actual value AQ) 
●  Up/down counter (Page 173) (actual value Cnt) 
●  Analog filter (Page 232) (actual value AQ) 
●  Average value (Page 237) (actual value AQ) 
●  Max/Min (Page 234) (actual value AQ) 
●  On-delay (Page 136) (current time Ta) 
●  Off-delay (Page 140) (current time Ta) 
●  On-/off-delay (Page 142) (current time Ta) 
●  Retentive on-delay (Page 144) (current time Ta)