Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 データシート

製品コード
6ED1057-3BA00-0AA8
ページ / 344
LOGO! functions 
 
4.4 Special functions list - SF 
 
LOGO! 
154
 
Manual, 06/2014, A5E33039675 
4.4.9 
Stairway lighting switch 
Short description 
An input edge triggers a configurable and retriggerable time. LOGO! resets the output after 
this time expires. LOGO! can optionally output a warning signal to warn of the impending 
time expiration.  
 
Symbol in LOGO! 
Wiring 
Description 
 
Input Trg 
A signal at input Trg (Trigger) triggers the off-delay 
time for the stairway lighting switch. 
Parameter 
T represents the off-delay time of the output (output 
signal transition 1 to 0). 
T
!
 determines the triggering time for the pre-warning. 
T
!L
 determines the length of the pre-warning signal. 
Retentivity:  
/ = No retentivity 
R = The status is retentive. 
Output Q 
LOGO! resets Q after the time T expires. LOGO! 
outputs a warning signal before this time expires. 
Parameter T, T
!
 and T
!L
 
Note the defaults of the T parameters listed in topic Time response (Page 128). 
The actual value of another already-programmed function can provide the off-delay time T, 
the pre-warning time T
!
 and the pre-warning period T
!L
. You can use the actual values of the 
following functions:  
●  Analog comparator  (Page 188) (actual value Ax – Ay) 
●  Analog threshold trigger (Page 183) (actual value Ax) 
●  Analog amplifier (Page 195) (actual value Ax) 
●  Analog multiplexer (Page 213) (actual value AQ) 
●  Analog ramp (Page 216) (actual value AQ) 
●  Mathematic instruction (Page 227) (actual value AQ) 
●  PI controller (Page 220) (actual value AQ) 
●  Up/down counter (Page 173) (actual value Cnt) 
●  Analog filter (Page 232) (actual value AQ) 
●  Average value (Page 237) (actual value AQ) 
●  Max/Min (Page 234) (actual value AQ) 
●  On-delay  (Page 136) (current time Ta) 
●  Off-delay  (Page 140) (current time Ta) 
●  On-/off-delay  (Page 142) (current time Ta)