LOGO! functions 
 
4.4 Special functions list - SF 
 
LOGO! 
158
 
Manual, 06/2014, A5E33039675 
Functional description 
A 0 to 1 transition at input Trg sets output Q. 
If output Q = 0, and input Trg is set hi at least for the duration of T
L
, LOGO! enables the 
permanent lighting function and sets output Q accordingly. 
LOGO! triggers the off-delay T when input Trg returns to 0 before T
L
 has expired. 
Output Q is reset when T
= T. 
You can output an off-warning signal prior to the expiration of the off-delay time (T - T
!
) that 
resets Q for the duration of the prewarning time period T
!L
. A subsequent signal at Trg 
always resets T and the output Q. 
If the block is retentive, LOGO! resets output Q and the expired time to the values before a 
power failure; if the block is not retentive, LOGO! resets output Q and the expired time to 
defaults after a power failure.  
Setting the Par parameter 
Note the defaults specified in the topic "Time response (Page 128)". 
 
 
Note 
T, T
!
 and T
!L
 must all have the same timebase. 
 
View in programming mode (example): 
 
View in parameter assignment mode (example):