Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 データシート

製品コード
6ED1057-3BA00-0AA8
ページ / 344
LOGO! functions 
 
4.4 Special functions list - SF 
 
LOGO! 
156
 
Manual, 06/2014, A5E33039675 
 
View in parameter assignment mode (example): 
 
4.4.10 
Multiple function switch 
Short description 
The multiple function switch provides two different functions:  
●  Pulse switch with off-delay 
●  Switch (permanent lighting) 
 
Symbol in LOGO! 
Wiring 
Description 
 
Input Trg 
A signal at input Trg (Trigger) sets output Q 
(permanent light) or resets Q with an off-delay. When 
active, output Q can be reset with a signal at input 
Trg. 
Input R 
A signal at input R resets the current time T
a
 and 
resets the output. 
Parameter 
T represents the off-delay time. LOGO! resets the 
output (1 to 0 transition) when time T expires. 
T
L
 represents the time during which the output must 
be set to enable the permanent light function. 
T
!
 represents the on-delay for the prewarning time. 
T
!L
 represents the length of the prewarning time 
period. 
Retentivity:  
/ = No retentivity 
R = The status is retentive. 
Output Q 
A signal at Trg switches on output Q. Depending on 
the length of the input at Trg, the output is off again or 
on permanently, or it is reset with a further signal at 
Trg.