4.4 Special functions list - SF 
LOGO! 
Manual, 06/2014, A5E33039675 
183
 
4.4.18 
Analog threshold trigger 
Short description 
The output is set and reset at two configurable thresholds.  
 
Symbol in LOGO! 
Wiring 
Description 
 
Input Ax 
Input Ax is one of the following analog signals:  
• 
AI1 to AI8 (*) 
• 
AM1 to AM64 
• 
NAI1 to NAI32 
• 
AQ1 to AQ8 
• 
NAQ1 to NAQ16 
• 
Block number of a function with analog output 
Parameter 
A: gain 
 Range of values: -10.00 to 10.00 
B: zero offset 
 Range of values: -10,000 to 10,000 
On: on threshold 
 Range of values: -20,000 to 20,000 
Off: off threshold 
 Range of values: -20,000 to 20,000 
p: number of decimals 
 Range of values: 0, 1, 2, 3 
Output Q 
Q is set or reset by the threshold triggers. 
* AI1...AI8: 0...10 V corresponds with 0...1000 (internal value). 
Gain and offset parameters 
Please note the information on gain and offset parameters in topic "Calculating the gain and 
Parameters On and Off 
The actual value of another already-programmed function can provide the On and Off 
parameters. You can use the actual values of the following functions:  
●  Analog comparator (Page 188) (actual value Ax – Ay) 
●  Analog amplifier (Page 195) (actual value Ax) 
●  Analog multiplexer (Page 213) (actual value AQ) 
●  Analog ramp (Page 216) (actual value AQ) 
●  Mathematic instruction (Page 227) (actual value AQ) 
●  PI controller (Page 220) (actual value AQ) 
●  Up/down counter (Page 173) (actual value Cnt)