LOGO! functions 
 
4.4 Special functions list - SF 
 
LOGO! 
184
 
Manual, 06/2014, A5E33039675 
●  Analog filter (Page 232) (actual value AQ) 
●  Average value (Page 237) (actual value AQ) 
●  Max/Min (Page 234) (actual value AQ) 
●  On-delay (Page 136) (current time Ta) 
●  Off-delay (Page 140) (current time Ta) 
●  On-/off-delay (Page 142) (current time Ta) 
●  Retentive on-delay (Page 144) (current time Ta) 
●  Wiping relay (pulse output) (Page 146) (current time Ta) 
●  Edge-triggered wiping relay (Page 148) (current time Ta) 
●  Asynchronous pulse generator (Page 150) (current time Ta) 
●  Stairway lighting switch (Page 154) (current time Ta) 
●  Multiple function switch (Page 156) (current time Ta) 
●  Stopwatch (Page 171) (actual value AQ) 
●  Analog threshold trigger (actual value Ax) 
●  Threshold trigger (Page 180) (actual value Fre) 
Select the required function by the block number. 
Parameter p (number of decimals) 
Applies only to the display of On, Off and Ax values in a message text. 
Does not apply to the comparison of On and Off values. (The compare function ignores the 
decimal point.) 
Timing diagram 
 
Functional description 
The function fetches the analog signal at input Ax.  
Ax is multiplied by the value of the A (gain) parameter, and the value at parameter B (offset) 
is added to product, i.e. (Ax • gain) + offset = actual value of Ax. 
Output Q is set or reset, depending on the set thresholds. See the calculation rule below.