Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 データシート

製品コード
6ED1057-3BA00-0AA8
ページ / 344
Technical data 
 
A.8 Technical data: LOGO! 12/24... LOGO! DM8 12/24R 
 
LOGO! 
306
 
Manual, 06/2014, A5E33039675 
 
LOGO! 12/24RCEo 
LOGO! 12/24RCE 
LOGO! DM8 12/24R 
Voltage failure buffering 
• 
12 VDC 
• 
24 VDC 
 
• 
Typ. 2 ms 
• 
Typ. 5 ms 
 
• 
Typ. 2 ms 
• 
Typ. 5 ms 
Power loss  
• 
12 VDC 
• 
24 VDC 
 
• 
0.4 W to 1.7 W 
• 
0.4 W to 2.2 W 
 
• 
0.2 W to 1.0 W 
• 
0.3 W to 1.0 W 
Backup of the real-time clock at 
25 °C 
Typ. 20 days 
- - 
Accuracy of the real-time clock   Typ. ± 2 s/day 
- - 
Electrical isolation 
No 
No 
Digital inputs 
Number 
Electrical isolation 
No 
No 
Number of high speed inputs 
4 (I3, I4, I5, I6) 
Input frequency 
• 
Normal input 
• 
High speed input 
 
• 
Max. 4 Hz 
• 
Max. 5 kHz 
 
• 
Max. 4 Hz 
• 
- - 
Max. continuous permissible 
voltage 
28.8 VDC 
28.8 VDC 
Input voltage L+  
• 
Signal 0 
• 
Signal 1 
 
• 
< 5 VDC 
• 
> 8.5 VDC 
 
• 
< 5 VDC 
• 
> 8.5 VDC 
Input current at 
• 
Signal 0 
 
• 
Signal 1 
 
< 0.88 mA (I3 to I6) 
< 0.07 mA (I1, I2, I7, I8) 
> 1.5 mA (I3 to I6) 
> 0.12 mA (I1, I2, I7, I8) 
 
< 0.88 mA 
 
> 1.5 mA 
Delay time at  
• 
0 to 1 
 
• 
1 to 0 
 
• 
Typ. 1.5 ms 
<1.0 ms (I3 to I6) 
• 
Typ. 1.5 ms 
<1.0 ms (I3 to I6) 
 
• 
Typ. 1.5 ms 
 
• 
Typ. 1.5 ms 
Line length (unshielded) 
Max. 100 m 
Max. 100 m 
Analog inputs 
Number 
4 (I1=AI3, I2=AI4, I7=AI1, I8=AI2)  - - 
Range 
0 VDC to 10 VDC  
Input impedance 72 kΩ 
- - 
Cycle time for analog value 
generation 
300 ms 
- - 
Line length (shielded and 
twisted) 
Max. 10 m 
- - 
Error limit 
± 1.5% at FS 
- -