Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 データシート

製品コード
6ED1057-3BA00-0AA8
ページ / 344
 
Technical data 
 
A.8 Technical data: LOGO! 12/24... LOGO! DM8 12/24R 
LOGO! 
Manual, 06/2014, A5E33039675 
305
 
 
LOGO! DM8 24R 
LOGO! DM16 24R 
Fluorescent tubes with ballast 
(25000 switching cycles) 
10 x 58 W 
10 x 58 W 
Fluorescent tubes, 
conventionally compensated 
(25000 switching cycles) 
1 x 58 W 
1 x 58 W 
Fluorescent tubes, 
uncompensated (25000 
switching cycles) 
10 x 58 W 
10 x 58 W 
Derating 
None; across the entire 
temperature range 
None; across the entire 
temperature range 
Short circuit-proof cos 1  
Power protection B16, 600 A 
Power protection B16, 600 A 
Short circuit-proof cos 0.5 to 0.7  Power protection B16, 900 A 
Power protection B16, 900 A 
Parallel output circuits for power 
increase 
Not permitted 
Not permitted 
Protection of output relay (if 
desired) 
Max. 16 A, 
characteristic B16 
Max. 16 A, 
characteristic B16 
Switching rate  
Mechanical 
10 Hz 
10 Hz 
Ohmic load/lamp load 
2 Hz 
2 Hz 
Inductive load 
0.5 Hz 
0.5 Hz 
Notice: For fluorescent lamps with capacitors, you must consider the technical data of 
fluorescent lamp ballasts. If the current exceeds the maximum allowed surge current, 
appropriate contactor relays must switch the flourescent lamps.  
The data was determined with the following devices: 
●  Siemens fluorescent tubes 58 W VVG 5LZ 583 3-1 uncompensated. 
●  Siemens fluorescent tubes 58 W VVG 5LZ 583 3-1 parallel compensated with 7 μF. 
●  Siemens fluorescent tubes 58 W VVG 5LZ 501 1-1N with ballast. 
A.8 
Technical data: LOGO! 12/24... LOGO! DM8 12/24R 
 
 
LOGO! 12/24RCEo 
LOGO! 12/24RCE 
LOGO! DM8 12/24R 
Power supply 
Input voltage 
12/24 VDC 
12/24 VDC 
Permissible range  
10.8 VDC to 28.8 VDC 
10.8 VDC to 28.8 VDC 
Reverse polarity protection 
Yes 
Yes 
Power consumption 
• 
12 VDC 
• 
24 VDC 
 
• 
30 mA to 140 mA 
• 
15 mA to 90 mA 
 
• 
10 mA to 80 mA 
• 
10 mA to 40 mA