A.18 Technical data: LOGO! CSM230 
LOGO! 
Manual, 06/2014, A5E33039675 
317
 
A.18 
Technical data: LOGO! CSM230 
The CSM230 is a communications switch module with Ethernet. It can support the current 
range of 100 VAC to 240 VAC and 115 VDC to 210 VDC. 
 
 
LOGO! CSM230 
Ethernet interface 
Communications connector 
4 x RJ45 jacks with MDI-X assignment 10/100 Mbps (half/full 
duplex), autopolarity, autonegotiation 
Network cable 
Use a shielded Ethernet cable to connect to the Ethernet interface. 
To minimize electromagnetic interference, make sure you use a 
standard Category 5 shielded twisted-pair Ethernet cable with a 
shielded RJ45 connector on each end. 
Largest data packet 
1518 bytes 
Smallest data packet 
64 bytes 
Delay resulting from latency 
When a frame passed through the CSM12/24, the stored and 
forward function of the switch delays the frame according to the 
characteristics below: 
• 
with a 64 bytes frame length by approx. 8 μs (at 100 Mbps). 
• 
with a 1518 bytes frame length by approx. 125 μs (at 100 
Mbps). 
Topology 
Star and bus topology 
Note that the direct connection of two ports on the switch or 
accidental connection over several switches causes an illegal loop. 
Such a loop can lead to network overload and network failures. 
Insulation of the ports 
You need shield all ports with each other that adhere to 1.5 kV 
insulation voltage. 
Learnable MAC addresses 
1024 
Aging time 
300 seconds 
Electrical specification 
Input voltage 
100 VAC to 240 VAC 
115 VDC to 210 VDC 
Permitted line power frequency  AC 47 Hz to 63 Hz 
Current consumption 
100 VAC to 240 VAC: 0.05 A to 0.03 A 
115 VDC to 210 VDC: 0.02 A to 0.012 A 
Effective power loss 
1.8 W 
Connection 
Per terminal for L+ and M 
Cable cross section: 1 x 2.5 mm
2
 or 2 x 1.5 mm
2
 
Tightening torque 0.57 Nm (5 lb in) 
Use 75 °C conductors only. Use copper conductors only. 
Functional grounding 
You can achieve functional grounding by connecting a cable from 
terminal 3, for example to the DIN rail. 
Keep this cable as short as possible. 
Grounding is, however, not necessary for interference-free 
operation. 
Further technical specifications