Siemens SPS starter kit 6ED1057-3BA00-0AA8 12 Vdc, 24 Vdc 6ED1057-3BA00-0AA8 データシート

製品コード
6ED1057-3BA00-0AA8
ページ / 344
 
LOGO! 
Manual, 06/2014, A5E33039675 
319
 
 
Determining the cycle time 
 
The program cycle is the complete execution of the circuit program, that is, primarily the 
reading in of the inputs, the processing of the circuit program and the subsequent writing the 
outputs. The cycle time is the time required to execute a circuit program once in full. 
You can determine the time required for a program cycle using a short test program. Create 
this test program in LOGO! to return a value from which you can calculate the cycle time. 
Test program 
To program this test program, follow these steps: 
1.  Create the test program by linking an output to a threshold trigger and connecting the 
trigger input with an inverted flag. 
 
2.  Configure the threshold trigger as shown below. LOGO! generates a pulse in each 
program cycle due to the inverted flag. The trigger interval is 2 seconds. 
 
3.  Now start the circuit program and switch LOGO! to parameter assignment mode. In this 
mode, view the trigger parameters. 
 
4.  The reciprocal value of f
a
 is equivalent to the LOGO! execution time of the current circuit 
program in its memory. 
 1/f
a
 = cycle time in s