LOGO! installation and wiring 
 
2.2 Installing/removing LOGO! 
 
LOGO! 
36
 
Manual, 06/2014, A5E33039675 
 LOGO! expansion modules, DM8 ..., AM... 
 LOGO! expansion modules, DM16 ... 
2.2.3 
Mounting the LOGO! TDE 
 
 
Note 
Make sure you mount the LOGO! TDE vertically on a flat surface of an IP 65 or Type 4X/12 
enclosure. 
 
To prepare the mounting surface for the optional LOGO! TDE and mount it, follow these 
steps: 
1.  Cut a 119 mm × 78.5 mm (tolerance: +0.5 mm) hole in the mounting surface. 
 
2.  Place the included gasket on the frontplate of the LOGO! TDE. 
3.  Fit the LOGO! TDE into the cutout you made in the mounting surface. 
4.  Attach the mounting brackets (included) to the LOGO! TDE. 
5.  Tighten the mounting screws on the mounting brackets to 0.2 Nm torque to secure the 
LOGO! TDE. 
 
 
 Mounting brackets 
 Mounting screws 
 Gasket 
 Cabinet door or control panel 
(Thickness: 1.5 mm to 4 mm) 
You can then connect the LOGO! TDE to the LOGO! Base Module through the Ethernet 
interface.