2.2.4 
Labeling LOGO! 
The rectangular areas on the LOGO! modules are intended for labeling. 
 
In the case of expansion modules, you can use the rectangular areas for labeling the inputs 
and outputs, for example. In this connection, you can enter a delta factor of +8 for the inputs 
or +4 for the outputs if the LOGO! Base Module already has 8 inputs or 4 outputs. 
2.3 
Wiring LOGO! 
Wire LOGO! using a screwdriver with a 3 mm blade. 
You do not need to wire ferrules for the terminals. You can use conductors fulfilled the 
following requirements: 
●  Cross-sections of up to the following thicknesses: 
–  1 × 2.5 mm
2
 
–  2 × 1.5 mm
for each second terminal chamber 
●  Conductor material: Cu 
●  Insulation temperature rating: 75 °C 
Tightening torque: 0.5 Nm to 0.6 Nm or 4.5 in-lbf to 5.3 in-lbf. 
 
 
Note 
Always cover the terminals after you have completed the installation. To protect LOGO! 
adequately from impermissible contact to live parts, comply with local standards. 
 
2.3.1 
Connecting the power supply 
The 230 V versions of LOGO! are suitable for operation with rated voltages of 115 VAC/VDC 
and 240 VAC/VDC. The LOGO! 24 V and 12 V versions can be operated with a 24 VDC, 
24 VAC or 12 VDC power supply. For information on permissible voltage tolerances, line 
frequencies and power consumption, refer to the installation instructions in the Product 
Information supplied with your device and to the technical data in Appendix A.