Murr Elektronik 9000-41034-0100400 MICO CLASSIC 4.4 - 4-Channel Electronic Auxiliary Circuit, 9000-41034-0100400 データシート

製品コード
9000-41034-0100400
ページ / 6
 
  
  Idx.  Datum
Gepr.
Data sheet 
  
 
a  31.08.09
Pan
 
  
 
l  13.09.10
ms
MICO 4.4 
Control imp.&consumption 
10.09.10 
ri Ges. 
4 channel 
Überarbeitet 07.04.10 
as 
 
i UL-Sicherh.werte 
01.10.09 
sb 
 
 
sheet 
UR Zeich. UL2367 
25.05.09 
ri 
Art.-No.: 9000-41034-0100400
1
Idx. Änderung Datum
 
Nam. 
 
3
Bl.
a Erstausgabe 
27.11.06 
as 
9000-41034-0100400_db_e_l 
 
 
 
Technische Änderungen vorbehalten / We reserve the right to change this specification             Schutzvermerk ISO 16016 beach
ten / Refer to protection notice ISO 16016 
Vom EDV-System heruntergeladene bzw. ausgedruckte Dokumente besitzen informativen Charakter und unterliegen nicht dem Änderungs
dienst / Documents downloaded by the EDP system and/or printed out have only an informative character and are not subject to th
e updating service 
 
turn ON capacity 
: max. 20mF* 
 
accuracy of disconnecting characteristic 
: 0...+20% 
 internal 
fuse
 : 
4A delay fuse for each channel  
 
 
(UL 248-14, UL File E10480) 
*  Dependent on:  component tolerance, conductor length, used power supply, load current, selected current range 
 
Control output: 
summation message output
 
: pontential-free message output 
 
switching voltage 
: max. 30 VAC/DC 
 
switching current 
: max. 100mA 
 
Additional data: 
measurements LxWxD 
: 90 x 70 x 80 mm 
 
 
weight 
: ca. 160g 
 connection 
type
 
: spring-clamp terminals 
 
environmental temperature 
-25°C*         0…+55°C 
 
 
* only with CE 
 
Relative humidity 
: 5%  -  85% Thawing not permissible
 
 
storing temperature 
: -40…+80°C 
 using 
category 
DC-1, DC-3, DC-5, DC-6, DC-20, DC-21, DC-22, DC-23 
 fastening
 
: snatch able on mounting rail TH 35  
 
 
: according to EN60715 
 
mounting position 
: vertical / distance unnecessary for multiple modules  
 
 
regulations 
 
 
: CE- producer statement 
 
isolation voltage rating 
: 50V, EN 60664-1 
 
degree of pollution 
: 2 
 
classification of over-voltage 
: III 
 
EN 60529 Protective system 
: IP 20 
 
mechanical test 
: EN 60068-2-6 oscillating test 
 
 
: 05 - 57,551 Hz; const. amplitude 0,15mm 
 
 
: 57,551 - 500 Hz: const. acceleration 
 
 
: EN 60068-2-27 shock test 
 
 
: 15g, 11ms duration 
 
EMC test 
: EN 61000-6-2 immunity to interference class A 
 
 
: EN 61000-6-3 interference emission class B 
 
Terminal range profiles: 
 
input 
: max. 16mm² AWG 06  
 
output 
: max. 4mm² AWG 12 / min. 0,5mm² AWG 20  
 
control input-/ output 
: max. 2,5mm² AWG 12 
 
GND 
: max. 4mm² AWG 12 
 
Function advice: 
The module initialization time amounts to generally 250ms. The GND-connection of the equipment merely serves to 
supply the internal electronics. GND of the load must be conducted directly to the power supply with separate wires. 
The electrical conductor profile and conductor lengths must be adapted to the set current range! Please pay attention to 
the wire capability in relationship of its cross section, ambient temperature, current as well as the used protection. The 
in 4 levels settable channel current serves as the conductor protection and device protection conform to EN60204-1, 
referring to the maximal permissible channel current.  
 
Attention:     
 
            
- Parallel switching of multiple channels for increase of power is not permitted. 
 
- Series connection of several MICO module to produce selective switch-off-characteristic is not 
 
  allowed. 
 
- A generated voltage at output is not allowed to be durably higher than the input voltage.