Murr Elektronik 9000-41034-0100400 MICO CLASSIC 4.4 - 4-Channel Electronic Auxiliary Circuit, 9000-41034-0100400 Ficha De Dados
Códigos do produto
9000-41034-0100400
Idx. Datum
Gepr.
Data sheet
a 31.08.09
Pan
l 13.09.10
ms
MICO 4.4
l
Control imp.&consumption
10.09.10
ri Ges.
4 channel
k
Überarbeitet 07.04.10
as
i UL-Sicherh.werte
01.10.09
sb
sheet
h
UR Zeich. UL2367
25.05.09
ri
Art.-No.: 9000-41034-0100400
1
Idx. Änderung Datum
Nam.
3
Bl.
a Erstausgabe
27.11.06
as
9000-41034-0100400_db_e_l
Technische Änderungen vorbehalten / We reserve the right to change this specification Schutzvermerk ISO 16016 beach
ten / Refer to protection notice ISO 16016
Vom EDV-System heruntergeladene bzw. ausgedruckte Dokumente besitzen informativen Charakter und unterliegen nicht dem Änderungs
dienst / Documents downloaded by the EDP system and/or printed out have only an informative character and are not subject to th
e updating service
turn ON capacity
: max. 20mF*
accuracy of disconnecting characteristic
: 0...+20%
internal
fuse
:
4A delay fuse for each channel
(UL 248-14, UL File E10480)
* Dependent on: component tolerance, conductor length, used power supply, load current, selected current range
Control output:
summation message output
: pontential-free message output
switching voltage
: max. 30 VAC/DC
switching current
: max. 100mA
Additional data:
measurements LxWxD
: 90 x 70 x 80 mm
weight
: ca. 160g
connection
type
: spring-clamp terminals
environmental temperature
-25°C* 0…+55°C
* only with CE
Relative humidity
: 5% - 85% Thawing not permissible
storing temperature
: -40…+80°C
using
category
:
DC-1, DC-3, DC-5, DC-6, DC-20, DC-21, DC-22, DC-23
fastening
: snatch able on mounting rail TH 35
: according to EN60715
mounting position
: vertical / distance unnecessary for multiple modules
regulations
: CE- producer statement
isolation voltage rating
: 50V, EN 60664-1
degree of pollution
: 2
classification of over-voltage
: III
EN 60529 Protective system
: IP 20
mechanical test
: EN 60068-2-6 oscillating test
: 05 - 57,551 Hz; const. amplitude 0,15mm
: 57,551 - 500 Hz: const. acceleration
: EN 60068-2-27 shock test
: 15g, 11ms duration
EMC test
: EN 61000-6-2 immunity to interference class A
: EN 61000-6-3 interference emission class B
Terminal range profiles:
input
: max. 16mm² AWG 06
output
: max. 4mm² AWG 12 / min. 0,5mm² AWG 20
control input-/ output
: max. 2,5mm² AWG 12
GND
: max. 4mm² AWG 12
Function advice:
The module initialization time amounts to generally 250ms. The GND-connection of the equipment merely serves to
supply the internal electronics. GND of the load must be conducted directly to the power supply with separate wires.
The electrical conductor profile and conductor lengths must be adapted to the set current range! Please pay attention to
the wire capability in relationship of its cross section, ambient temperature, current as well as the used protection. The
in 4 levels settable channel current serves as the conductor protection and device protection conform to EN60204-1,
referring to the maximal permissible channel current.
Attention:
- Parallel switching of multiple channels for increase of power is not permitted.
- Series connection of several MICO module to produce selective switch-off-characteristic is not
allowed.
- A generated voltage at output is not allowed to be durably higher than the input voltage.