Bryan Boilers HE-CLM Series プリント

ページ / 2
Quality Construction Features
A.  Heavy steel boiler frame, built and stamped in accordance 
with the ASME Boiler Code, Section IV.
B.  Large  volume  water leg  down comers  promote  rapid internal 
circulation, temperature equalization and effi cient heat transfer.
C.  Bryan bent water tubes are fl exible, individually replaceable with-
out welding or rolling. Never more than two tube confi gurations. 
D.  Boiler  tube  and  furnace  area  access panel: heavy gauge 
steel casing with 2" high temperature ceramic  fi ber and insulation, 
bolted and tightly sealed to boiler frame.
E.  Jacket access panels make the interior of the boiler easily 
accessible for service and inspection.
F.  Steel boiler jacket with 16 gauge rust-resistant zinc coating 
and attractive enamel fi nish,  insulated with 1½" fi berglass to insure 
exceptionally cool outer surface.
G.  Minimum sized fl ue vent. 
H. Forced draft, fl ame retention head type burner. Effi cient 
combustion and quiet operation. 
I.   All controls, gauges, relief valve(s) are factory installed and 
wired and easily accessible for servicing.
J.  Electrical box: all controls installed and connected to terminal 
strip.
K .  Water side interior accessible for cleanout and inspection, 
front and rear openings, upper and lower drums.
L.  Steel plate boiler base with lightweight, high temperature 
insulating fi rebrick combustion chamber, designed for maximum 
combustion effi ciency.
Form No. 6700
(Rev. 5/07)
Guaranteed 85% 
 effi ciency
•   With HE-CLM Series Boilers,  
 
you get a guaranteed 85%  
 combustion 
effi ciency result- 
 
ing from a uniquely designed  
 
integrated extended surface  
 heat 
extractor.
•   What's more, HE-CLM Boilers  
 
offer high operating 
 effi ciency—at all normal  
 operation 
temperatures— 
 
 
without the complications 
 
of condensation concerns.
Bryan HE-CLM Series Boiler Specifi cations
Bryan “Flexible Water Tube”
HE-CLM Series Water Boilers
900,000 to 3,000,000 BTUH
Forced draft gas fi red
Originators of the “Flexible Water Tube” design
Model HE-CLM300-W-FDG
 BOILER            INPUT            OUTPUT @ 85% EFFICIENCY
(1)
    HTG.SURFACE    APPROX. SHIP
 MODEL         MBH (KW)            MBH (KW) 
   HP (KW)          SQ.FT.(M
2
)            LBS. (KG)
HE-CLM90
          900 (264) 
765 (224) 
  23 (224) 
   171 (15.9)           2,110 (957) 
HE-CLM120
       1,200 (352)           1,020 (299)  
  30 (299) 
    227 (21.1)           2,400 (1,089) 
HE-CLM150
       1,500 (440)           1,275 (374)  
  38 (374) 
    282 (26.2)           2,860 (1,297) 
HE-CLM180
       1,800 (527)           1,530 (448)  
  46 (448) 
    338 (31.4)           3,200 (1,452)
HE-CLM210
       2,100 (615)           1,785 (523) 
  53 (523) 
    394 (36.6)           3,740 (1,697) 
HE-CLM240
       2,400 (703)           2,040 (598)  
  61 (598) 
    451 (41.9)           4,200 (1,905) 
HE-CLM270
       2,700 (791)           2,295 (672)  
  69 (672) 
    506 (47.0)           4,740 (2,150) 
HE-CLM300
       3,000 (879)           2,550 (747)  
  76 (747) 
    564 (52.4)           5,175 (2,348) 
NOTES : (1) Output and horsepower based on an average natural gas combustion effi ciency of 85%.