Consideration must be given to all possible condi-
tions and their consequences. 
Piping With Refrigeration Machines 
When used with a refrigeration system, the boiler 
shall be installed so that chilled medium is piped in 
parallel with the boiler.  Valves should be installed 
to prevent chilled water from entering the boiler 
when the system is operated in the cooling mode. 
Piping With Air Handling Units 
The boiler piping system of a hot water heating 
boiler connected to heating coils located in air han-
dling units, where they may be exposed to refriger-
ated air circulation, must be equipped with flow 
control valves or other automatic means to prevent 
gravity circulation of the boiler water during the 
cooling cycle. 
 
3.8.2  Boiler Inlet and Outlet Connections 
 
 
 
 
 
 
Boiler Inlet and Outlet Connections 
 
Make water connections as the application warrants, 
or at a minimum, as shown, but always in compli-
ance with the local requirements. 
Note: Pipe unions and isolating valves must be 
installed in both water connections for ease of 
service.
 
The bottom connection to the boiler is the INLET 
and must be used for the return from the system. 
The top connection to the boiler is the OUTLET and 
must be connected as the supply to the system. 
Piping must be installed such that no piping stresses 
are transmitted to the boiler.  The boiler should not 
be used as a pipe anchor. 
 
3.8.3  Boiler Water Piping by Installer 
 
Strainer 
To avoid possible contamination of the boiler with 
dirt, rust or sediment from the system, a strainer 
near the boiler inlet is strongly recommended.  Even 
new systems may contain sufficient foreign material 
to eventually reduce the performance of the heat 
exchanger.  Adequate circulation of good clean wa-
ter is essential to maximum efficiency and long life 
of the boiler. 
 
 
Relief Valve and Piping 
Each boiler is supplied with a pressure-relief valve 
sized in accordance with ASME requirements.  The 
relief valve should be piped to a suitable floor drain.  
Reducing couplings or other restrictions are not 
permitted in the discharge line. 
 
 
Low Water Cut-off 
The boiler is furnished with a flow-switch-type low 
water cut-off as required by Section IV ASME 
Code; no field piping is required.  If the flow switch 
does not sense water flow, the boiler will shut down 
and a red indicator will be illuminated on the control 
panel.  This flow switch only proves that flow is 
present.  It does not prove adequate flow as required 
by this boiler.  
Installation of an external low water cutoff or man-
ual reset low-water switch may be required by cer-
tain codes or in certain installations.  Consult your 
local code for details. 
 