Honeywell Excell 500/600 Controll System 500-XCL5010 ユーザーズマニュアル

ページ / 48
EXCEL 500/600 INSTALLATION INSTRUCTIONS 
XC5010C / XC6010 Cable Lengths and Sizes 
A cable length of 1300 ft (400m) with a cross sectional area of 
0.5 mm
2
 (20 AWG) is permissible for a two-core, 0 to 10 Vdc
Table 3. Cable sizing 
signal cable. 
Type of signal 
Cross sectional area 
≤≤≤≤ 300 ft 
(100 m) 
≤≤≤≤ 550 ft 
(170 m) 
≤≤≤≤ 1300 ft 
(400 m) 
24 Vac power 
supply 
≤ 16 AWG 
(
≥ 1.5 mm
2
≤ 14 AWG 
(
≥ 2.5 mm
2
-
Low voltage 
signals
≤ 20 AWG (≥ 0.5 mm
2
0 to 10V sensors, totalizers, digital inputs, 0 to 10V signals for 
actuators, etc. 
Lightning Protection 
Please contact your local Honeywell representative for 
information on lightning protection. 
MAX. 1300 ft (400 m) 
EXTERNAL 
TRANSFORMER 
MIN. 20AWG (0.5 mm2) 
24 Vac 
230 Vac 
120 Vac 
PRIMARY 
VOLTAGE 
TRANSFORMER 
PRIMARY 
VOLTAGE 
Y
24 Vac 
24 V 
GND 
Fig. 44. Connection of XL500/600 controller and a 24 V
actuator with separate transformers 
21 
EN1R-1047GE51 R0902