EXCEL 500/600 INSTALLATION INSTRUCTIONS 
Line Power Supply
 WARNING 
A separate CRT 6 or 1450 series (U.S.) transformer must be  
used for each of the EXCEL 500/600 controller's 24 V supply.  
No additional loads may be connected !  
Each additional XL500/600 controller requires its own  
transformer.  
An additional transformer, appropriate to the power require­
ments, should be used to power input/output peripherals (e.g.  
actuators).  
MAX. 1300 ft (400 m) 
MIN. 20 AWG (0.5 mm2) 
PRIMARY 
VOLTAGE 
EXTERNAL 
TRANSFORMER 
24 Vac 
230 Vac 
120 Vac 
PRIMARY 
VOLTAGE 
TRANSFORMER 
Y
24 Vac 
24 V 
GND 
Fig. 45. Connection of XL500/600 controller and a 24V
actuator with separate transformers 
Primary 
Secondary 
220 VAC 
230 VAC 
+ 6 % 
-10 % 
+10 % 
-15 % 
24 VAC  ±20% 
CB-0039a 
Fig. 46. Excel 500/600 power supply 
To avoid interference, the cable between the transformer and 
the power supply module should be kept as short as possible 
(max. 6 ft (2m)). The transformer should therefore be 
positioned close to the power supply module. 
Fuse the transformer primary with its own fast-acting 10 A 
back-up fuse (or H 16 or L 16 miniature circuit breaker). 
The primary coil of the CRT 6 contains a 0.8 A / 250 V quick­
blow fuse. 
Table 5 gives an overview of the transformers of the 1450 
series (U.S.): 
Table 5. 1450 series transformers data 
Part # 
1450 7287 
Primary
side 
Secondary side 
-001 
120 Vac 
24 Vac, 50 VA 
-002 
120 Vac 
2 x 24 Vac, 40 VA, and 100 VA 
from separate transformer 
-003 
120 Vac 
24 Vac, 100 VA, and 24 Vdc; 
600 mA 
-004 
240/220 Vac  24 Vac, 50 VA 
-005 
240/220 Vac 
2 x 24 Vac, 40 VA, and 100 VA 
from separate transformer 
-006 
240/220 Vac 
24 Vac, 100 VA, and 24 Vdc; 
600 mA 
The 1450 series includes built-in fuses, line transient /surge 
protection and AC convenience outlet, it meets NEC class 2 
requirements. 
XC6010 Computer Module
 CAUTION 
Do not unplug the computer module with the power 
still connected, since this could destroy the module. 
First, switch S1 on the power supply module to the 0 
position. 
If one of the C-bus submodules XD505A or XD508 is installed 
on the XC6010, follow Fig. 47. 
Fig. 47. Excel 600 CPU module C-Bus connections 
The system bus is connected to terminal 16 (C+) and terminal 
17 (C-). See also section "C-Bus Termination (Excel 600)" o
page 38. 
If the XDM506 Modem Submodule is installed on the 
XC6010, follow Fig. 48. Use the XW571 modem cable to 
connect the appropriate modem to the wiring terminals. 
23 
EN1R-1047GE51 R0902