EXCEL 500/600 INSTALLATION INSTRUCTIONS 
Fig. 50. Excel 600 submodule mounting location 
For information pertaining to system bus baud rates and 
termination switch settings, see section "C-Bus Termination 
(Excel 600)"
 on page 38. 
Fig. 48. Excel 600 CPU modem connection 
The XC6010 has 2 EPROMs for the operating system and 
one flash EPROM for the application software. Their locations 
are shown in Fig. 49. 
Fig. 49. Excel 600 EPROM locations 
Communication between several Excel 600 controllers is 
possible only if the system bus submodule is plugged into 
every computer module printed circuit board. This submodule 
must be installed when joining several controllers, when 
connecting a modem, or when monitoring via a central. 
XD505A or XD508 can be used for local bus communication, 
XDM506 is used for modem communication. A stand-alone 
controller can be operated without a submodule. 
XC5010C Computer Module
 CAUTION 
Do not unplug the computer module with the power 
still connected, since this could destroy the module. 
First, switch S1 on the power supply module to the 0 
position. 
The XC5010C computer module contains both the system 
bus and the field bus. Fig. 51 shows the pin-out of the 
module. 
Fig. 51. Excel 500 CPU module pin-out 
The system bus is connected to terminal 16 (C+) and terminal 
17 (C-). The field bus (L
ON
W
ORKS 
bus) is connected to 
terminals 12 and 13. The L
ON
W
ORKS
 bus is non-polarized, i.e. 
there is no + or – pin. See section "L
(page 36) and "System Bus (C-Bus)" (page 37) for more 
information. 
EN1R-1047GE51 R0902 