EXCEL 500/600 INSTALLATION INSTRUCTIONS 
MOUNTING 
Control Unit Installation 
The Excel 500 and 600 controllers have the same housing 
and can be installed two different ways: 
—   Installation inside a control panel (see page 8)
—   Installation through a control panel door (see page 10). 
Fig. 1. Excel 500/600 panel door mounting 
The Excel 500-XCL5010 can be mounted only on a DIN rail; 
control panel door installation is not possible. 
Fig. 2. Excel 500-XCL5010 DIN rail mounting 
Excel 500/600 Housing Layout (not XCL5010) 
A controller comprises from one to a maximum of five 
housings. The housings may be fitted alongside one another 
or, one above the other. Any combination is possible. 
Fig. 3. Up to five housings can be connected together 
When housings are alongside one another, a minimum 
spacing of 1.5 in. (35 mm) should be taken into consideration 
to enable the hinged cover to be opened. The maximum 
spacing between housings is limited by tailor-made internal 
bus cables as shown in Fig. 3. 
Excel 500/600 Internal Bus Wiring (not
XCL5010) 
Each housing has four plug-in module locations. The 
individual modules are connected by an internal bus in the 
housing. 
Configurations comprising more than one housing must have 
the individual busses in the housings connected to one 
another. 
Fig. 4. Excel 500/600 bus wiring 
The connection is made via tailor-made ribbon cables. Two 
different types are available: 
—   Type XW568 3 in. (80 mm) long (for housings alongside 
one another) 
EN1R-1047GE51 R0902