EXCEL 500/600 INSTALLATION INSTRUCTIONS 
Setting the Module Address (not XCL5010) 
In the case of application prior to CARE 4.0, you can set the 
module address using the rotary HEX switches located on the 
upper surface of the respective input and output modules. 
The rotary HEX switch of Distributed I/O modules is situated 
within the housing. The XP502 power supply module and the 
XC5010C / XC6010 computer modules do not need a 
hardware address. 
Fig. 8. Internal module HEX switch location 
The 16 I/O modules (max. including Distributed I/O) are 
addressed by means of the rotary HEX switch settings 0 to F. 
Fig. 9. Close-up of HEX addressing switch 
The relationship between the rotary HEX switch and the 
module address can be seen on the label located next to the 
rotary HEX switch. 
Fig. 10. HEX switch label 
Care should be taken to ensure that each module gets its 
own module address. Addressing the modules in ascending 
order 0 through F is recommended for the sake of clarity for 
maintenance personnel.
 CAUTION 
Unplugging a module before switching OFF the power 
supply could destroy the module. Do not unplug 
modules with the power still connected. First switch 
S1 on the power supply module to the 0 position. 
Installation Inside a Control Panel 
Excel 500/600 
IMPORTANT 
Observe the minimum spacing of 1.5 in. (35 mm) 
when installing more than one housing. Do not ex-
ceed the maximum spacing; otherwise, the tailor-
made internal bus cables will be too short. 
1.  Break off cable entry strip segments. 
Fig. 11. Cable entry strip segments 
2.  Install the base. 
Fig. 12. Installing the base in the panel 
EN1R-1047GE51 R0902