Beck, R&J ELECTRIC ACTUATORS FOR INDUSTRIAL PROCESSCONTROL 11-1_9 ユーザーズマニュアル

ページ / 88
17
INSTALLATION
 SIGNAL WIRING
 
Each Beck drive is custom built to match the 
control requirements of your system specified 
at the time of order.  Each drive has a specific 
wiring diagram attached to the inside of the wiring 
terminal cover.  Typical wiring connections are 
described below.    
 
A drive can be ordered with up to four optional 
auxiliary switches.  Wiring connections for these 
are described on page 26.
 
To prevent Handswitch initiated motion,  
remove the jumper between terminals A and C.  
CAUTION:  AC power to the drive must be 
turned off before removing the jumper.
Typical Wiring Connections
POWER AND DEMAND
INPUT CONNECTIONS
 
Customer must supply 120 V ac to power the 
drive and control circuitry.  120 V ac line connects 
to terminal C and neutral to terminal B.  Input signal 
wires connect to terminals AA (+) and BB (–).